Induced transients in substation cables: measurements and models

An extensive set of switching transient EMI response measurements on several types of substation cables and internal cable wires is described in this paper. Measured and predicted cable/wire current and voltage transients at both air-insulated substations (AIS) and gas-insulated substations (GIS) ar...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1994-10, Vol.9 (4), p.1861-1868
Hauptverfasser: Thomas, D.E., Wiggins, E.M., Salas, T.M., Nickle, F.S., Wright, S.E.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:An extensive set of switching transient EMI response measurements on several types of substation cables and internal cable wires is described in this paper. Measured and predicted cable/wire current and voltage transients at both air-insulated substations (AIS) and gas-insulated substations (GIS) are presented, for system voltages ranging from 115 kV to 500 kV. The maximum peak-to-peak amplitudes of measured wire transients are found to vary from around 1 A to almost 20 A (current in amperes), and from 0.3 kV to almost 7 kV (voltage in kilovolts). Predictive models for field-driven coupling, as well as for direct-driven coupling via current transformers or capacitively-coupled voltage transformers (CTs/CCVTs), are presented. Model predictions are compared to and validated against measured wire transients.< >
ISSN:0885-8977
1937-4208
DOI:10.1109/61.329519