Effects of deteriorated and contaminated substation surface covering layers on foot resistance calculations

It is shown that significant inaccuracies can occur when the ANSI/IEEE Std 80 method for calculating foot resistances is applied in substations covered by a thin layer of crushed rock or similar covering layers. In particular, the errors obtained by using the infinite series expression of the foot r...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1993-01, Vol.8 (1), p.104-113
Hauptverfasser: Dawalibi, F.P., Xiong, W., Ma, J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:It is shown that significant inaccuracies can occur when the ANSI/IEEE Std 80 method for calculating foot resistances is applied in substations covered by a thin layer of crushed rock or similar covering layers. In particular, the errors obtained by using the infinite series expression of the foot resistance are consistently larger than those produced by the simplified expression for clean and contaminated surface layers.< >
ISSN:0885-8977
1937-4208
DOI:10.1109/61.180325