Neumann Series Based Voltage Sensitivity Analysis for Three Phase Distribution System
In this letter, a simplified voltage sensitivity analysis technique that can provide accurate estimates of voltage change across the network for a given change in bus power injections in a three-phase unbalanced distribution network is proposed. This technique is derived from the first-order approxi...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power systems 2022-07, Vol.37 (4), p.3145-3148 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In this letter, a simplified voltage sensitivity analysis technique that can provide accurate estimates of voltage change across the network for a given change in bus power injections in a three-phase unbalanced distribution network is proposed. This technique is derived from the first-order approximation of the Neumann series, which allows maintaining the accuracy of the solution while the computational effort is reduced. The proposed technique is tested on a 559-bus unbalanced distribution system with multiple distributed generation resources. The results show that the average error in the voltage estimates with the proposed method is not more than 0.3% with the execution time of similar order relative to the state-of-the-art sensitivity analysis methods. |
---|---|
ISSN: | 0885-8950 1558-0679 |
DOI: | 10.1109/TPWRS.2022.3156435 |