Neumann Series Based Voltage Sensitivity Analysis for Three Phase Distribution System

In this letter, a simplified voltage sensitivity analysis technique that can provide accurate estimates of voltage change across the network for a given change in bus power injections in a three-phase unbalanced distribution network is proposed. This technique is derived from the first-order approxi...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power systems 2022-07, Vol.37 (4), p.3145-3148
Hauptverfasser: Kumar R, James Ranjith, Natarajan, Balasubramaniam, Pahwa, Anil
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this letter, a simplified voltage sensitivity analysis technique that can provide accurate estimates of voltage change across the network for a given change in bus power injections in a three-phase unbalanced distribution network is proposed. This technique is derived from the first-order approximation of the Neumann series, which allows maintaining the accuracy of the solution while the computational effort is reduced. The proposed technique is tested on a 559-bus unbalanced distribution system with multiple distributed generation resources. The results show that the average error in the voltage estimates with the proposed method is not more than 0.3% with the execution time of similar order relative to the state-of-the-art sensitivity analysis methods.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.2022.3156435