Experimental study of the seawater fouling on a plate-frame heat exchanger for utilization of waste heat from powerplant
The overall heat transfer coefficient, pressure drop, and the fouling thermal resistance were compared between a clean and a seawater-exposed, fouled plate-frame heat exchanger. The fouled heat exchanger was utilized for heat recovery from the seawater-effluent for 3 months at a powerplant site. The...
Gespeichert in:
Veröffentlicht in: | Journal of mechanical science and technology 2019, 33(10), , pp.5025-5032 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The overall heat transfer coefficient, pressure drop, and the fouling thermal resistance were compared between a clean and a seawater-exposed, fouled plate-frame heat exchanger. The fouled heat exchanger was utilized for heat recovery from the seawater-effluent for 3 months at a powerplant site. The performance tests were conducted at temperatures of 20 °C and 30 °C on the fouled-side, while the corresponding temperatures on the clean-side were 15 °C and 25 °C, respectively. Flow rate ranged from 20 to 40 l·min
−1
on the fouled-side and the clean-side of the heat exchanger. In the absence of fouling, the average U value was higher than that under the fouling condition by 21.3 %. The average thermal resistance ranged from 0.135 m
2
·K·kW
−1
to 0.157 m
2
·K·kW
−1
. The pressure drop was less than 2 kPa with the change of temperature, but the pressure drop of the fouled-side increased by 400 % compared with that of the clean-side. |
---|---|
ISSN: | 1738-494X 1976-3824 |
DOI: | 10.1007/s12206-019-0941-6 |