A study on the evaluation of ventilation system suitable for outside air cooling applied in large data center for energy conservation
In developed countries, expansion of communication technology has resulted in continual increase in the construction of data centers with high-density cooling loads. Throughout a year, IT equipment installed in a data center generates large and constant cooling load. As a result, data centers may be...
Gespeichert in:
Veröffentlicht in: | Journal of mechanical science and technology 2016, 30(5), , pp.2319-2324 |
---|---|
1. Verfasser: | |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In developed countries, expansion of communication technology has resulted in continual increase in the construction of data centers with high-density cooling loads. Throughout a year, IT equipment installed in a data center generates large and constant cooling load. As a result, data centers may be consuming an ever-growing amount of energy. The cooling system utilizing the energy of outside air is applied universally to reduce data center energy consumption. The application of the cooling system to the outdoor air cooling system of a data center considers that temperature efficiency and ventilation performance vary depending on the type of ventilation system. The displacement and mixed ventilation method can be applied generally to a data center. The efficiency of a ventilation system depends on inside temperature or contaminant concentrations in room and outlets. This study thus aims to evaluate the ventilation performance that varies according to type of ventilation system installed in the data center. Ventilation efficiency is assessed by applying the concept of total air age and considers the fresh air ratio and age of return air. Further, temperature efficiency gained by utilizing temperature difference is used to assess causes for changes in ventilation performance. |
---|---|
ISSN: | 1738-494X 1976-3824 |
DOI: | 10.1007/s12206-016-0441-x |