Accelerating Aging of Transmission Line Porcelain Suspension Insulators by Autoclaving
Porcelain suspension insulators aged for 1, 5 and 10 years on Korean transmission lines and new insulators are tested for autoclave expansion. The compressive strength of the insulators aged in an autoclave with conditions of $250\;^{\circ}C$ and at 20 atm for 30 minutes, was about $7.6\;kgf/mm^2$,...
Gespeichert in:
Veröffentlicht in: | Transactions on electrical and electronic materials 2008-08, Vol.9 (4), p.147-150 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | kor |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Porcelain suspension insulators aged for 1, 5 and 10 years on Korean transmission lines and new insulators are tested for autoclave expansion. The compressive strength of the insulators aged in an autoclave with conditions of $250\;^{\circ}C$ and at 20 atm for 30 minutes, was about $7.6\;kgf/mm^2$, which is close to that measured on insulators aged for 10 years in the field. From simulation results, the cement displacement changed linearly with temperature. At a temperature of $200\;^{\circ}C$, the shear stress was approximately $7\;kgf/mm^2$; a stress that is brought about by a 0.07 % expansion of the cement. It is evident that the cement would fracture at a 0.07 % expansion, because the cement has about 7 to $9\;kgf/mm^2$ flexure strength. A turning point in the shear stress with mechanical load occurred at 0.02 % cement expansion. From an analysis of the porcelain body it is shown that there is sufficient margin of strength to guard against fracture of the porcelain body even for a cement expansion more than 0.12 %. |
---|---|
ISSN: | 1229-7607 2092-7592 |