The impact of inrush currents on the mechanical stress of high voltage power transformer coils

From failure experience on power transformers, it was very often suspected that inrush currents, occurring when energizing unloaded transformers, were reason for damage. In this paper, it was investigated how mechanical forces within the transformer coils build up under inrush compared to those occu...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2002-01, Vol.17 (1), p.155-160
Hauptverfasser: Steurer, M., Frohlich, K.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:From failure experience on power transformers, it was very often suspected that inrush currents, occurring when energizing unloaded transformers, were reason for damage. In this paper, it was investigated how mechanical forces within the transformer coils build up under inrush compared to those occurring at short circuit. Two-dimensional and three-dimensional computer modeling for a real 268 MVA, 525/17.75 kV three-legged step up transformer was employed. The results show that inrush current peaks of 70% of the rated short circuit current cause local forces in the same order of magnitude as those at short circuit. The resulting force summed up over the high voltage coil is even three times higher. Although inrush currents normally are smaller, the forces can have similar amplitudes as those at short circuit however with longer exposure time. Therefore, care has to be taken to avoid such high inrush currents. Today controlled switching offers an elegant and practical solution.
ISSN:0885-8977
1937-4208
DOI:10.1109/61.974203