A novel technique for detecting electromagnetic wave caused by partial discharge in GIS

For the insulation diagnosis of GIS, it is necessary to detect partial discharge (PD) under noisy condition and to specify the direction of electromagnetic wave radiation due to PD. We proposed "phase gate control method" for discriminating the electromagnetic wave caused by PD in SF/sub 6...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2001-10, Vol.16 (4), p.545-551
Hauptverfasser: Hoshino, T., Kato, K., Hayakawa, N., Okubo, H.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:For the insulation diagnosis of GIS, it is necessary to detect partial discharge (PD) under noisy condition and to specify the direction of electromagnetic wave radiation due to PD. We proposed "phase gate control method" for discriminating the electromagnetic wave caused by PD in SF/sub 6/ gas from external noises. The proposed method enabled us to discriminate PD of about 100 pC in SF/sub 6/ gas from external noises of more than 10000 pC in air. We also compared polarization characteristics of electromagnetic wave radiated from PD with those from a half-wave dipole antenna, and could estimate the radiation length of electromagnetic wave caused by PD. The results derived in this paper contribute to the insulation diagnosis of GIS on-site.
ISSN:0885-8977
1937-4208
DOI:10.1109/61.956735