Measurement and Analysis of PMU Reporting Latency for Smart Grid Protection and Control Applications
Emerging power system protection and control applications require faster-responding measurements and more accurate knowledge of the actual latency of the measurement and communications systems. A new method for accurately determining the reporting latency of a phasor measurement unit (PMU) has been...
Gespeichert in:
Veröffentlicht in: | IEEE access 2019, Vol.7, p.48689-48698 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Emerging power system protection and control applications require faster-responding measurements and more accurate knowledge of the actual latency of the measurement and communications systems. A new method for accurately determining the reporting latency of a phasor measurement unit (PMU) has been developed and demonstrated. This method operates in real-time, works passively for any existing PMU without requiring changes to the PMU hardware or software, and it is very accurate-providing a measurement uncertainty of ¡500 ns in many cases, significantly surpassing the 0.002 s accuracy requirement in the most recent IEEE Synchrophasor standard. Only low-cost hardware and open source software are required. It is particularly important to understand end-to-end system latency, including the impact of local and wide-area communications, rather than just the latency of the PMU device; the proposed method also supports such practical measurements. It is therefore shown how this advance can be used to enable efficient, but realistic, cross-domain power system simulation studies, which incorporate measurement and communications delays. These capabilities address complexity and uncertainty in the design and operation of future PMU-based protection and control functions for new smart grid services. |
---|---|
ISSN: | 2169-3536 2169-3536 |
DOI: | 10.1109/ACCESS.2019.2903929 |