Integral system for energy storage and power generation uses Written-Pole/sup TM/ AC motor and DC generator plus flywheel and gas engine; eliminates batteries at cellular sites
A Written-Pole/sup TM/ brand of variable magnetic pole AC motor is used to drive a generator to produce DC power to be used in place of batteries and rectifiers for critical loads. The motor-generator set starts with low inrush current, has very high inertia, and uses flywheel energy storage to ride...
Gespeichert in:
Hauptverfasser: | , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A Written-Pole/sup TM/ brand of variable magnetic pole AC motor is used to drive a generator to produce DC power to be used in place of batteries and rectifiers for critical loads. The motor-generator set starts with low inrush current, has very high inertia, and uses flywheel energy storage to ride-through momentary power interruptions while the DC output remains very stable. An internal combustion engine is integrally mounted on the M-G sets and is used to drive the system during long, extended utility outages. The engine is started using the M-G set inertia instead of a battery. The Written-Pole/sup TM/ motor converts to a generator while the engine is the prime mover. This supplies AC power for loads such as air conditioners for electronics. The system has been field-tested and is in commercial production. |
---|---|
DOI: | 10.1109/INTLEC.1998.793639 |