Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents
A common load on a distribution feeder consists of a combination single-phase lighting load and a three-phase load such as an induction motor. This combination load can be served by a wye-delta transformer bank. The question is whether the wye connection should be directly connected to ground, conne...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on industry applications 2017-01, Vol.53 (1), p.65-70 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A common load on a distribution feeder consists of a combination single-phase lighting load and a three-phase load such as an induction motor. This combination load can be served by a wye-delta transformer bank. The question is whether the wye connection should be directly connected to ground, connected to ground through a grounding resistor or left ungrounded. During normal loading conditions, each connection has advantages and disadvantages. However, during a short-circuit condition, a grounded wye-delta bank will provide a "backfeed" short-circuit current for an upstream ground fault. This paper will develop methods for the analysis of the backfeed currents for an upstream line-to-ground fault. |
---|---|