Analysis of November 29, 2005 Western American Oscillation Event
The letter discusses the oscillation event of November 29, 2005 in the western American power system when a 20 MW forced oscillation in Alberta led to 200 MW oscillations on the California-Oregon Inter-tie lines. Using archived synchrophasor data from the event, this letter shows that the large ampl...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power systems 2016-11, Vol.31 (6), p.5210-5211 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The letter discusses the oscillation event of November 29, 2005 in the western American power system when a 20 MW forced oscillation in Alberta led to 200 MW oscillations on the California-Oregon Inter-tie lines. Using archived synchrophasor data from the event, this letter shows that the large amplitude tie-line oscillations were caused by a resonance between the forced oscillations and the 0.25 Hz inter-area western system mode. Specifically the letter shows that resonance occurred even though the system mode was well-damped during the event because of the oscillation frequency and location of the forced oscillations. |
---|---|
ISSN: | 0885-8950 1558-0679 |
DOI: | 10.1109/TPWRS.2016.2521319 |