Fault Location Using Sparse Synchrophasor Measurement of Electromechanical-Wave Oscillations

This paper presents a novel system-wide fault-location method for transmission lines utilizing electromechanical-wave oscillation propagation phenomena. The method uses synchrophasor measurements during disturbances obtained from phasor measurement units sparsely located in the network. The method d...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2016-08, Vol.31 (4), p.1787-1796
Hauptverfasser: Esmaeilian, Ahad, Kezunovic, M.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents a novel system-wide fault-location method for transmission lines utilizing electromechanical-wave oscillation propagation phenomena. The method uses synchrophasor measurements during disturbances obtained from phasor measurement units sparsely located in the network. The method determines the time of arrival of electromechanical waves propagating from the fault point to sparsely located phasor measurement units. By taking the speed of electromechanical-wave propagation as well as topology of the network into account, the method is able to detect the faulty line. Finally, by adding fictitious buses inside the faulty line and applying a binary search method, the location of fault is accurately pinpointed. The main advantage of the proposed method is the use of a limited number of PMUs which reduces the cost of implementation. The method was developed in MATLAB and tested with the IEEE 118-test system. Test results reveal the high accuracy of the method in detecting and locating faults.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2015.2510585