Lightning-Induced Voltages in the Presence of Nearby Buildings: FDTD Simulation Versus Small-Scale Experiment

In this paper, we have computed lightning-induced voltages on overhead distribution lines in the presence of nearby buildings using the 3-D finite-difference time-domain method. In the simulations, four-conductor lines with surge arresters and pole transformers are considered. It appears that the pr...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on electromagnetic compatibility 2015-12, Vol.57 (6), p.1601-1607
Hauptverfasser: Tran Huu Thang, Baba, Yoshihiro, Piantini, Alexandre, Rakov, Vladimir A.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this paper, we have computed lightning-induced voltages on overhead distribution lines in the presence of nearby buildings using the 3-D finite-difference time-domain method. In the simulations, four-conductor lines with surge arresters and pole transformers are considered. It appears that the presence of nearby buildings causes reduction of lightning induced voltages, as expected. The observed trend is in general agreement with that reported from the small-scale experiment by Piantini et al.
ISSN:0018-9375
1558-187X
DOI:10.1109/TEMC.2015.2457951