Analysis and Control of Bipolar LVDC Grid With DC Symmetrical Component Method

The dc symmetrical component method is introduced for the analysis and control of bipolar dc distribution systems under asymmetrical operation. This method is an extension of the classical symmetrical component theory in three-phase ac power systems. The asymmetrical voltage and current in the posit...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power systems 2016-01, Vol.31 (1), p.685-694
Hauptverfasser: Gu, Yunjie, Li, Wuhua, He, Xiangning
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The dc symmetrical component method is introduced for the analysis and control of bipolar dc distribution systems under asymmetrical operation. This method is an extension of the classical symmetrical component theory in three-phase ac power systems. The asymmetrical voltage and current in the positive and negative poles are decomposed into symmetrical components in common and differential modes. The equivalent circuit for each mode is derived, which forms decoupled mode networks. Consequently, it allows for independent investigation of each mode, and provides an insightful view of the static and dynamic behavior of a bipolar dc power system. The dc symmetrical component method is a general approach which is applicable to different aspects of system design. As an example, an enhanced common-mode voltage regulation scheme is described. It suppresses common-mode LC resonance by adding active damping control, and reduces common-mode impedance to improve power quality and voltage stability. The major theoretical conclusions are verified by experimental results.
ISSN:0885-8950
1558-0679