Characteristics of the voltage and current in singlephase faults on reactored transmission lines

Because of using a fixed-time, present single-phase reclosure techniques on transmission lines have poor ability of detecting non-fault before reclosing. It is necessary to detect non-fault to avoid unsuccessful reclosing in arcing faults or permanent faults. Then it is essential to improve the effe...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Shao Wenquan, Zhang Xiaowei, Song Jiangxi, Nan Shugong
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Because of using a fixed-time, present single-phase reclosure techniques on transmission lines have poor ability of detecting non-fault before reclosing. It is necessary to detect non-fault to avoid unsuccessful reclosing in arcing faults or permanent faults. Then it is essential to improve the effectiveness of the non-fault detection based on reliable data. Therefore, this paper discussed the amplitudes of the terminal-voltage and the current in the shunt reactor under different fault conditions in single-phase arcing faults and non-arc faults respectively. The results show that the current is more reliable than the voltage in most arcing faults and non-arc faults, so it is feasible to employ comprehensive criterion using voltage and current for increasing the accuracy of the non-fault detection.