Experimental Research on Suppressing VFTO in GIS by Magnetic Rings

Very-fast transient overvoltage (VFTO) is a serious threat to the insulation of extra-high voltage and ultra-high voltage power-system equipment and should be suppressed. A simpler and more reliable VFTO suppressing method than a shunt resistor is presented in this paper, which uses magnetic rings i...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2013-10, Vol.28 (4), p.2558-2565
Hauptverfasser: Guan, Yonggang, Yue, Gongchang, Chen, Weijiang, Li, Zhibing, Liu, Weidong
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Very-fast transient overvoltage (VFTO) is a serious threat to the insulation of extra-high voltage and ultra-high voltage power-system equipment and should be suppressed. A simpler and more reliable VFTO suppressing method than a shunt resistor is presented in this paper, which uses magnetic rings installed on the center conductor of gas-insulated switchgear (GIS). Two kinds of magnetic materials that can work under high frequency were adopted, one of which is ferrite R2KB and the other is amorphous FJ37. Measurements in a scale model with an air-insulated busbar show that ferrite R2KB rings have a better suppressing effect than amorphous FJ37 when the ring-cluster length is larger than a certain value. The ferrite R2KB rings were applied to 252-kV GIS. The test results show that ferrite R2KB rings can significantly suppress the peak value and the time to peak of VFTO. When the ring-cluster length is 40 cm and the test voltage is 140 kV of power frequency, the overshoot factor and the front steepness of VFTO can be reduced more than 50% and 20%, respectively. The test results are exiting and indicate that using magnetic rings to suppress VFTO is feasible.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2013.2278462