An assessment on aging model of IEEE/IEC standards for natural and mineral oil-immersed transformer
This paper presents an assessment on aging model of IEEE and IEC standards using thermal model of oil-immersed power transformer for natural ester and mineral oil. For this purpose, a model created for the analysis of behavior transient thermal performance with aging both of natural ester and minera...
Gespeichert in:
Hauptverfasser: | , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents an assessment on aging model of IEEE and IEC standards using thermal model of oil-immersed power transformer for natural ester and mineral oil. For this purpose, a model created for the analysis of behavior transient thermal performance with aging both of natural ester and mineral oils. Thermal model of the transformer is based on thermal-electrical analogy that is calculated separately for natural and mineral oils covering top-oil and hot-spot temperatures. The hot-spot temperature values of each ester/oil are used to calculate aging parameters which include the aging acceleration factor, time dependent relative aging rate and insulation life loss variations. |
---|---|
ISSN: | 2153-3725 2153-3733 |
DOI: | 10.1109/ICDL.2011.6015442 |