Determining distance relay Zone-1 reach settings to prevent CCVT transient overreach
This paper presents the results of a study on determining Zone-1 reach settings for transmission line distance relays to prevent overreach resulting from coupling capacitor voltage transformer (CCVT) transients. In particular, this study focused on digital distance relays and determining appropriate...
Gespeichert in:
Hauptverfasser: | , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents the results of a study on determining Zone-1 reach settings for transmission line distance relays to prevent overreach resulting from coupling capacitor voltage transformer (CCVT) transients. In particular, this study focused on digital distance relays and determining appropriate relay reach settings to account for the effects of CCVT transients during faults for CCVTs with active ferroresonant suppression circuits. The results of the study presented herein are based on EMTP simulations that were validated by actual relay tests. |
---|---|
ISSN: | 1091-0050 1558-058X |
DOI: | 10.1109/SECON.2011.5752892 |