A Case Study on Lightning Protection, Current Injection Measurements, and Model

A newly built pharmaceutical plant has been investigated by measurements. Currents of 0.3 kA were injected in the lightning protection grid on the roof. Inside the building, test cables of 100 m length followed a path typical for cables belonging to the installation. We measured induced cable curren...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on electromagnetic compatibility 2010-08, Vol.52 (3), p.684-690
Hauptverfasser: Bargboer, Geesje, van Deursen, Alexander P. J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A newly built pharmaceutical plant has been investigated by measurements. Currents of 0.3 kA were injected in the lightning protection grid on the roof. Inside the building, test cables of 100 m length followed a path typical for cables belonging to the installation. We measured induced cable currents and voltages. A reduced model of the building incorporated most of the designed current paths. Measurements and model showed that the roof steel skeleton carried about 80% of the current and the intended lightning conductors 20%. The calculated current through a cable support was larger than measured. This is explained by also considering a nearby nonintended conductor. For three types of cables, we determined the transfer impedances. The measurements and model have been combined and extrapolated to actual lightning.
ISSN:0018-9375
1558-187X
DOI:10.1109/TEMC.2010.2050486