Ground fault protection for DC bus using controlled power sequencing
We present a new approach to protect a multi-branch medium-voltage DC bus from ground faults. Behavior analysis of a DC distribution scheme shows that it is possible to quickly de-energize the DC bus by controlling the main converter, open a contactor to remove the faulted line, then re-energize the...
Gespeichert in:
Hauptverfasser: | , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | We present a new approach to protect a multi-branch medium-voltage DC bus from ground faults. Behavior analysis of a DC distribution scheme shows that it is possible to quickly de-energize the DC bus by controlling the main converter, open a contactor to remove the faulted line, then re-energize the system. This strategy reduces the out-of-service time and avoids the use of mechanical circuit breakers and their arc-eliminating equipments. The fast response time allows unfaulted loads to ride through the process with minimal local energy storage. Our research shows that it is possible to de-energize, reconfigure, and re-energize a typical industrial DC bus 10-20 times faster than methods traditionally applied in AC circuits, and that only 470 ¿Farad of bus capacitance is needed for unfaulted circuits to ride-through the process uninterrupted. |
---|---|