Improved operating scheme using an IEC61850-based distance relay for transformer backup protection

Problems occur when zones overlap in the conventional step distance protection scheme. If the same zones from different relays overlap, discriminating between the real fault location and the virtual one is difficult, and malfunction can occur. In this case, the zone length or time delay is usually m...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Hyung-Kyu Kim, Sang-Hee Kang, Soon-Ryul Nam, Sea-Seung Oh
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Problems occur when zones overlap in the conventional step distance protection scheme. If the same zones from different relays overlap, discriminating between the real fault location and the virtual one is difficult, and malfunction can occur. In this case, the zone length or time delay is usually modified to separate the overlapped zones. However, these changes affect the coordination of the power protection system. A clear example of this involves transformer backup protection. Generally, when Zone 2 of a transformer backup protection relay overlaps Zone 2 of an adjacent line backup protection, the method of modifying this zone may not be obvious. To overcome this problem, this paper describes an improved operating scheme using an IEC61850-based distance relay for transformer backup protection.
DOI:10.1109/PTC.2009.5282235