Reactive Power Compensation in Distribution Networks with STATCOM by Fuzzy Logic Theory Application
In this paper a STATCOM using fuzzy logic controller to compensate reactive power in distribution networks is developed. The advantage of fuzzy control is that it is based on a linguistic description and does not require a mathematical model of the system. The performance of the fuzzy logic controll...
Gespeichert in:
Hauptverfasser: | , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In this paper a STATCOM using fuzzy logic controller to compensate reactive power in distribution networks is developed. The advantage of fuzzy control is that it is based on a linguistic description and does not require a mathematical model of the system. The performance of the fuzzy logic controller is compared with a conventional PI controller and results are presented under steady state and transient condition. The plusmn3MVAR STATCOM is connected to the 20 kV B 2 bus through a 20 kV/2 kV Wye/Delta transformer. On this 20 MVA inductive network, the plusmn3MVAR STATCOM can correct voltage dip of plusmn12%. The secondly voltage is synthesized by a pulse width modulation inverter (PWM) using a 2.5 kHz chopping frequency |
---|---|
DOI: | 10.1109/IPEMC.2006.4778097 |