Non-Uniform Field Breakdown of Ar +SF6 under Negative Polarity Impulse Voltages

In this study, negative-polarity, standard lightning impulse voltages with different magnitudes were employed throughout the experiments. The percentage of SF 6 in Ar was varied from 1% to 90% and from 1% to 75% at a total gas pressure of 50 kPa and 100 kPa, respectively. The breakdown voltage of ea...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Hiziroglu, H.R., Dincer, M.S.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this study, negative-polarity, standard lightning impulse voltages with different magnitudes were employed throughout the experiments. The percentage of SF 6 in Ar was varied from 1% to 90% and from 1% to 75% at a total gas pressure of 50 kPa and 100 kPa, respectively. The breakdown voltage of each gas mixture was recorded at 50% breakdown probability. Similar to earlier studies under static electric fields it is observed that the breakdown voltages of Ar+SF 6 has increased dramatically when mixed with a small percentage of SF 6 under impulse voltages. However, the breakdown voltages were found to be higher than positive polarity, non-uniform and uniform fields.
ISSN:0084-9162
2576-2397
DOI:10.1109/CEIDP.2008.4772763