Out-of-step protection using the equal area criterion in time domain - SMIB and 3-machine case studies

This paper introduces a new method to detect out-of-step condition in power system based on an energy equilibrium criterion in the time domain directly. The proposed criterion is obtained using the concepts of equal area criterion in power angle domain but eliminates the need for numerical computati...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Paudyal, S., Ramakrishna, G., Sachdev, M.S.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper introduces a new method to detect out-of-step condition in power system based on an energy equilibrium criterion in the time domain directly. The proposed criterion is obtained using the concepts of equal area criterion in power angle domain but eliminates the need for numerical computations required in the earlier algorithm. The proposed algorithm uses power-time curve for computing the system transient energy to detect the stability of the system. The effectiveness of the proposed algorithm is tested on a single machine infinite bus and a three machine infinite bus system. The simulation results show that the proposed algorithm is general, accurate and applicable to complex power systems.
ISSN:2159-3442
2159-3450
DOI:10.1109/TENCON.2008.4766466