Onsite Calibration of a Current Transformer Using a Rogowski Coil
This paper describes a reference current-measuring system for the onsite calibration of high-voltage current transformers. The reference current-measuring system consists of a Rogowski coil, a current shunt, two digitizing voltmeters, and a computer to control the voltmeters. The method of generatio...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on instrumentation and measurement 2009-04, Vol.58 (4), p.1054-1058 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper describes a reference current-measuring system for the onsite calibration of high-voltage current transformers. The reference current-measuring system consists of a Rogowski coil, a current shunt, two digitizing voltmeters, and a computer to control the voltmeters. The method of generation of the high current and the uncertainty of the calibration are discussed. The results of a calibration performed onsite on a 400-kV substation are presented. Uncertainties of 300 muA/A for ratio and 1 angular minute for phase displacement were achieved with this method onsite. |
---|---|
ISSN: | 0018-9456 1557-9662 |
DOI: | 10.1109/TIM.2008.2007031 |