RSFCL optimum shunt resistance determination to enhance power system transient stability

In power systems, resistor type superconducting fault current limiters (RSFCL) can limit the prospective short circuit currents to lower levels, so that the underrated switchgears can operate safely. Besides, RSFCLs can enhance the power system transient stability if they are accompanied by appropri...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Hooshyar, H., Savaghebi, M.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In power systems, resistor type superconducting fault current limiters (RSFCL) can limit the prospective short circuit currents to lower levels, so that the underrated switchgears can operate safely. Besides, RSFCLs can enhance the power system transient stability if they are accompanied by appropriate shunt resistances. This paper presents a method of optimum shunt resistance determination for transient stability improvement. The method is based on minimization of rotor kinetic energy oscillations. Meanwhile to make it more comprehensible, the method is utilized to determine the shunt resistances of three RSFCLs installed in a 9-bus 3-generator sample network. All of the simulations have been carried out by EMTP/ATP.
DOI:10.1109/UPEC.2008.4651609