New PD measurement method for high power transformer PDM in service operation
Partial discharge measurement is a kind of effective condition check method for high power transformer. Normally, when a high power transformer needs to be checked by partial discharge measurement periodically, outage is required. Here, a newly developed measurement method for transformer is introdu...
Gespeichert in:
Hauptverfasser: | , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Partial discharge measurement is a kind of effective condition check method for high power transformer. Normally, when a high power transformer needs to be checked by partial discharge measurement periodically, outage is required. Here, a newly developed measurement method for transformer is introduced in which a new kind of capacitive coupling sensor is applied. The sensor consists of a pair of metal plates and a high frequency CT, which can be installed at the flange of the high voltage bushing of the transformer during the transformer in commercial service operation, without any outage. |
---|---|
DOI: | 10.1109/CMD.2008.4580436 |