On-site calibration of a current transformer using a Rogowski coil

This paper describes an outdoor calibration of an instrument current transformer connected to 400 kV transmission line. The method of generation of the high current and the accuracy of calibration are discussed. The reference current measuring system consists of a current shunt, a Rogowski coil, two...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Suomalainen, E.-P., Hallstrom, J.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper describes an outdoor calibration of an instrument current transformer connected to 400 kV transmission line. The method of generation of the high current and the accuracy of calibration are discussed. The reference current measuring system consists of a current shunt, a Rogowski coil, two digitizing voltmeters and a computer to control voltmeters. The Rogowski coil is calibrated on-site with the current shunt. The output voltage of the Rogowski coil is not integrated, but it is scaled according to the on-site calibration result. Estimated uncertainties for ratio and phase displacement are less than 0,01% and 100 murad, respectively.
ISSN:0589-1485
2160-0171
DOI:10.1109/CPEM.2008.4574856