Research on sympathetic interaction between transformers

The phenomenon of sympathetic interaction between transformers is discussed in this paper. A mathematical model is developed for two transformers in parallel and in series operation to analyze the origin mechanism of sympathetic interaction. At the same time, its characteristics are further analyzed...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Dejun Shao, Xianggen Yin, Zhe Zhang, Deshu Chen, Kanjun Zhang
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The phenomenon of sympathetic interaction between transformers is discussed in this paper. A mathematical model is developed for two transformers in parallel and in series operation to analyze the origin mechanism of sympathetic interaction. At the same time, its characteristics are further analyzed by numerical simulation. The sympathetic inrush current could influence the transformer differential protection. The physical dynamic simulation experiment results are analyzed, which prove the second harmonic restrain method could restrain the sympathetic inrush and the CT saturation criterion should be used for the differential protection.