CT Saturation Calculations - Are they Applicable in the Modern World? - Part II, Proposed Responsibilities
Part I expressed concerns about using IEEE Standard C37.110-1996 (1+X/R) criteria for sizing current transformers (CT's) for feeder short-circuit conditions [1]. Part II introduces an overview of relay filter algorithms, and proposes responsibilities of the IEEE Power System Relay Committee (PS...
Gespeichert in:
Hauptverfasser: | , , , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Part I expressed concerns about using IEEE Standard C37.110-1996 (1+X/R) criteria for sizing current transformers (CT's) for feeder short-circuit conditions [1]. Part II introduces an overview of relay filter algorithms, and proposes responsibilities of the IEEE Power System Relay Committee (PSRC), operating company and engineering company electrical power engineers, CT manufacturers, switchgear manufacturers, and relay manufacturers to guarantee CT/relay system performance. International Electrotechnical Commission (IEC) responsibilities are also included. |
---|---|
ISSN: | 0090-3507 2161-8127 |
DOI: | 10.1109/PCICON.2007.4365788 |