A Power Line Signaling Based Scheme for Anti-Islanding Protection of Distributed Generators-Part II: Field Test Results

Anti-islanding protection of distributed generators (DG) is a significant technical barrier to the emerging DG industry. In response to this challenge, a power line signaling based anti-islanding protection scheme has been proposed in a companion paper. The scheme broadcasts a signal from a substati...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2007-07, Vol.22 (3), p.1767-1772
Hauptverfasser: Wencong Wang, Kliber, J., Guibin Zhang, Wilsun Xu, Howell, B., Palladino, T.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Anti-islanding protection of distributed generators (DG) is a significant technical barrier to the emerging DG industry. In response to this challenge, a power line signaling based anti-islanding protection scheme has been proposed in a companion paper. The scheme broadcasts a signal from a substation to the DG sites using the distribution feeders as signal paths. A DG is considered as islanded from the upstream system if the signal is not detected at the DG site. This paper presents extensive field test results and experiences obtained for the proposed scheme. The results confirm that the proposed scheme is a very promising and economical method to satisfy anti-islanding protection requirements for synchronous DG interconnections.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2007.899620