A DEVELOPMENT OF IMPROVED UNDERGROUND DISTRIBUTION POWER CABLES

The root causes of underground distribution medium voltage cable faults are water penetration into insulation layer and stress enhancement on semi-conductive layers. Accordingly, it is needed to improve the waterproof performance of jacket materials and the structure of power cables for extending li...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Jae-Bong Lee, Ju-Yong Kim, Il-Keun Song, Byung-Sook Kim
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The root causes of underground distribution medium voltage cable faults are water penetration into insulation layer and stress enhancement on semi-conductive layers. Accordingly, it is needed to improve the waterproof performance of jacket materials and the structure of power cables for extending lifetime and preventing failure. We uses non-flaming polyethylene materials instead of PVC(polyvinyl chloride) as a outer jacket material and encapsulating structure. We also use super smooth class material as a inner semi-conductive layer. The newly developed cables have improved in AC breakdown voltage after ageing tests.
ISSN:2152-985X
2152-9868
DOI:10.1109/TDCLLM.2006.340745