A DEVELOPMENT OF IMPROVED UNDERGROUND DISTRIBUTION POWER CABLES
The root causes of underground distribution medium voltage cable faults are water penetration into insulation layer and stress enhancement on semi-conductive layers. Accordingly, it is needed to improve the waterproof performance of jacket materials and the structure of power cables for extending li...
Gespeichert in:
Hauptverfasser: | , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The root causes of underground distribution medium voltage cable faults are water penetration into insulation layer and stress enhancement on semi-conductive layers. Accordingly, it is needed to improve the waterproof performance of jacket materials and the structure of power cables for extending lifetime and preventing failure. We uses non-flaming polyethylene materials instead of PVC(polyvinyl chloride) as a outer jacket material and encapsulating structure. We also use super smooth class material as a inner semi-conductive layer. The newly developed cables have improved in AC breakdown voltage after ageing tests. |
---|---|
ISSN: | 2152-985X 2152-9868 |