Modified values for geometric factor of external thermal resistance of cables in duct banks

The authors previously described a technique for calculating the geometric factor G/sub b/ for extended ranges of the height/width ratio of the duct bank or backfill that enabled the Neher-McGrath method to be applied to a wider range of cable configurations. However, the technique was based on the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1988-10, Vol.3 (4), p.1303-1309
Hauptverfasser: El-Kady, M.A., Anders, G.A., Motlis, J., Horrocks, D.J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The authors previously described a technique for calculating the geometric factor G/sub b/ for extended ranges of the height/width ratio of the duct bank or backfill that enabled the Neher-McGrath method to be applied to a wider range of cable configurations. However, the technique was based on the assumption that the duct bank surface represents an isothermal boundary, which can result in some errors in the derived G/sub b/-values. A finite-element-based technique is described for calculating modified values of G/sub b/ on the basis of the actual heat-transfer mechanism (constant total heat flux) around the duct bank surface. The technique was applied to several cable configurations, yielding more accurate values.< >
ISSN:0885-8977
1937-4208
DOI:10.1109/61.193924