Cable Overheating in an Industrial Substation Feeder Due to Untransposed Power Cables - Measurement and Simulation
This paper presents measurements of asymmetrical current distribution among parallel connected cables on the secondary side of 20/0.4kV transformers. Overloading of some cables is shown to lead to premature cable ageing. Simulation of the situation by EMTP shows that simple and affordable cable layo...
Gespeichert in:
Hauptverfasser: | , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents measurements of asymmetrical current distribution among parallel connected cables on the secondary side of 20/0.4kV transformers. Overloading of some cables is shown to lead to premature cable ageing. Simulation of the situation by EMTP shows that simple and affordable cable layout - other than cable transposition - can significantly deteriorate the current asymmetries. The increase in cable temperature and losses as well as the deterioration of cable useful life is calculated for various cable configurations |
---|---|
DOI: | 10.1109/EURCON.2005.1630233 |