420 kV SF6-insulated tubular bus for the Wehr pumped-storage plant electric tests

Two 420 kV SF 6 -insulated tubular bus systems, 600m and 700m long, have been completed in the spring of 1975. The three-phase systems consist of isolated-phase transmission lines and form the power link for the Wehr pumped-storage plant. After a brief description of the electrical data specified an...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power apparatus and systems 1976-01, Vol.95 (2), p.469-477
Hauptverfasser: Baer, G.P., Diessner, A., Luxa, G.F.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Two 420 kV SF 6 -insulated tubular bus systems, 600m and 700m long, have been completed in the spring of 1975. The three-phase systems consist of isolated-phase transmission lines and form the power link for the Wehr pumped-storage plant. After a brief description of the electrical data specified and of the mechanical design, the authors describe the large number of electrical tests carried out. These included laboratory tests, which were concluded by type-testing of the tubular bus and metalclad surge diverter, and routine tests on insulators and diverters. Special attention was also paid to the performance of the equipment under various fictitious fault conditions, and several test series were carried out for this purpose. For the test at the site, an oscillating switching impulse voltage was applied.
ISSN:0018-9510
2995-6323
DOI:10.1109/T-PAS.1976.32126