Real-time Measurement Approach for Accurate Estimating the AV10 Value of EAF

This study investigates ac EAFs by making field measurements; with those results indicate that the estimated DeltaV 10 value obtained using the conventional method is significantly lower than the surveyed value. This paper found the DeltaQ max value of the original design is too small to respond the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Guan, J.L., Gu, J.C., Yang, M.T., Chang, H.H., Huang, C.L.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This study investigates ac EAFs by making field measurements; with those results indicate that the estimated DeltaV 10 value obtained using the conventional method is significantly lower than the surveyed value. This paper found the DeltaQ max value of the original design is too small to respond the actual variation of reactive power. Meanwhile, the difference of DeltaQ max between design value and actual value is quite big. However, this investigation suggests that the DeltaQ max estimate calculation must adopt a stricter standard. Therefore, we refer to the operation experience of manufacturers, namely that the biggest value of Costhetas r equals 1.0 for ac EAFs. Furthermore, surveyed results reveal that the revised method can yield more accurate DeltaV 10 estimates than traditional method
ISSN:2160-8636
2160-8644
DOI:10.1109/TDC.2005.1547114