Generator protection and CT-saturation problems and solutions
This paper presents a new generator relay design, stator differential function in particular, coping with extreme cases of current transformer (CT) saturation: both ac saturation under large currents and/or residual flux; and dc saturation under low currents but large and long-lasting dc components....
Gespeichert in:
Veröffentlicht in: | IEEE transactions on industry applications 2005-11, Vol.41 (6), p.1452-1457 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents a new generator relay design, stator differential function in particular, coping with extreme cases of current transformer (CT) saturation: both ac saturation under large currents and/or residual flux; and dc saturation under low currents but large and long-lasting dc components. The algorithm is a subcycle algorithm with fastest times reaching half a cycle including overall response of the relay hardware. Analysis of the response of a traditional differential function under CT saturation is included to provide setting guidelines for legacy relays. |
---|---|