Generator protection and CT-saturation problems and solutions

This paper presents a new generator relay design, stator differential function in particular, coping with extreme cases of current transformer (CT) saturation: both ac saturation under large currents and/or residual flux; and dc saturation under low currents but large and long-lasting dc components....

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industry applications 2005-11, Vol.41 (6), p.1452-1457
Hauptverfasser: Kasztenny, B., Finney, D.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents a new generator relay design, stator differential function in particular, coping with extreme cases of current transformer (CT) saturation: both ac saturation under large currents and/or residual flux; and dc saturation under low currents but large and long-lasting dc components. The algorithm is a subcycle algorithm with fastest times reaching half a cycle including overall response of the relay hardware. Analysis of the response of a traditional differential function under CT saturation is included to provide setting guidelines for legacy relays.
ISSN:0093-9994
1939-9367