Novel method to be applied for voltage flicker prediction caused by EAF

This investigation develops an enhanced method for estimating the voltage flicker of the electric arc furnace (EAF). The method not only considers the reactive power variation but also the active power variation in calculating the estimated /spl Delta/V/sub 10/ value of EAF. This study also consider...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Guan, J.L., Gu, J.C., Yang, M.T., Huang, C.L., Chang, H.H.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This investigation develops an enhanced method for estimating the voltage flicker of the electric arc furnace (EAF). The method not only considers the reactive power variation but also the active power variation in calculating the estimated /spl Delta/V/sub 10/ value of EAF. This study also considers field measurements of ac and dc EAFs. The results reveal that the estimated /spl Delta/V/sub 10/ value is significantly smaller than the observed value. The conventional way of estimating /spl Delta/V/sub 10/ is ineffective. The survey results demonstrate that variations of active power and reactive power of EAFs are strongly alike. Meanwhile, an /spl Delta/V/sub 10/ estimate must account for the effect of active power variation. However, this study proposes a maximum complex apparent power fluctuation method (MCAPFM) that can yield a more accurate /spl Delta/V/sub 10/ estimation than the conventional method.
ISSN:1932-5517
DOI:10.1109/PES.2005.1489382