Zero-crossing distortion in grid-connected PV inverters

Zero-crossing distortion has been observed in the ac output current produced by some grid-connected photovoltaic inverters and this can cause a resonant response between the grid impedance and the inverter filter capacitor. In some cases, particularly with large numbers of parallel-connected inverte...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industrial electronics (1982) 2005-04, Vol.52 (2), p.558-565
Hauptverfasser: Kotsopoulos, A., Heskes, P.J.M., Jansen, M.J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Zero-crossing distortion has been observed in the ac output current produced by some grid-connected photovoltaic inverters and this can cause a resonant response between the grid impedance and the inverter filter capacitor. In some cases, particularly with large numbers of parallel-connected inverters and with weak grids, the resonance can cause voltage distortion that may be large enough to disturb other nearby equipment. A number of commercially available inverters were tested to investigate the mechanisms of this distortion. A model was then developed to allow further simulations with different numbers of inverters and varying levels of distortion to be performed.
ISSN:0278-0046
1557-9948
DOI:10.1109/TIE.2005.844254