Transient short-circuit currents in auxiliary DC installations in power plants and substations
The original contribution of this work is contained in the following statements. A general mathematical model of auxiliary DC installations in power plants was developed in order to be used for analyzing short circuit conditions according to the references K. Albert et al. (1996). It was concluded t...
Gespeichert in:
Hauptverfasser: | , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The original contribution of this work is contained in the following statements. A general mathematical model of auxiliary DC installations in power plants was developed in order to be used for analyzing short circuit conditions according to the references K. Albert et al. (1996). It was concluded that the transient state during short circuit has to be taken into account. The essence of this new approach is the new mathematical model which takes into consideration not only resistances, but inductances and capacities of auxiliary DC elements as well as the active network in front of the rectifier. Based on this mathematical model, an original program package was developed and used for analyzing and dimensioning auxiliary DC installations in power plants according to A. Berizzi et al. (1998). The results obtained by means of the program package are relevant for dimensioning all elements of auxiliary DC installations, particularly when protection devices are considered. |
---|---|