Electric submersible pump grounding

Although ESPs have been produced for almost one hundred years, the actual causes of certain electrical failures are still unknown. Why do failures occur on start-up or two weeks after an electrical storm? Most of the answers to these questions can be found from an analysis of traditional grounding t...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Brinner, T.R., Atkins, J.D., Durham, M.O.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Although ESPs have been produced for almost one hundred years, the actual causes of certain electrical failures are still unknown. Why do failures occur on start-up or two weeks after an electrical storm? Most of the answers to these questions can be found from an analysis of traditional grounding techniques and consideration of how electrical insulation fails. ESPs are predominantly operated on ungrounded power, which can lead to arcing faults and residual charge. Frequently the wellhead is not even used as a ground. At other times cathodic protection installers insist on no other connections to the wellhead. Some ground wire connections can actually exacerbate the electrical damage done by lightning. Three-wire power systems are still quite prevalent in the oil field. Ferroresonance and lack of third-harmonic magnetizing current can produce very distorted waveforms. All these topic are investigated. A consensus seems to be building that one grounding configuration does provide superior reliability.