Location of partial discharges in shielded cables in the presence of high noise
Updated information on a partial discharge location system intended to pinpoint the location of defects and/or faults on a shielded buried underground cable is presented. The system is based on the principle of reflectometry. Its salient characteristics include the following two features: (a) an abi...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on electrical insulation 1992-02, Vol.27 (1), p.37-43 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Updated information on a partial discharge location system intended to pinpoint the location of defects and/or faults on a shielded buried underground cable is presented. The system is based on the principle of reflectometry. Its salient characteristics include the following two features: (a) an ability to pinpoint the location of a partial discharge source not only along the cable length, but also along the surface of the trench where it is buried; and (b) the ability to operate in a high noise environment. Recent field and laboratory data obtained on noise and techniques for its mitigation are discussed in some detail. These techniques include analog/digital notch filters for the elimination of AM broadcast noise and an adaptive digital filtering scheme which incorporates the transfer function of the cable for added accuracy.< > |
---|---|
ISSN: | 0018-9367 1557-962X |
DOI: | 10.1109/14.123439 |