Transient Angle and Voltage Stability of Grid-Forming Converters with Typical Reactive Power Control Schemes

Grid-forming converters have been identified as an enabling technology in more-electronic power systems. Nevertheless, the reactive power control of grid-forming converters has often been ignored during transients. This article innovatively points out the transient angle and/or voltage instability o...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE journal of emerging and selected topics in power electronics 2024-10, p.1-1
Hauptverfasser: Si, Wenjia, Fang, Jingyang, Chen, Xingyou, Xu, Tao, Goetz, Stefan M.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Grid-forming converters have been identified as an enabling technology in more-electronic power systems. Nevertheless, the reactive power control of grid-forming converters has often been ignored during transients. This article innovatively points out the transient angle and/or voltage instability of grid-forming converters with typical reactive power control schemes, comprising voltage, reactive power droop, and reactive power PI control schemes. We disclose that the grid-forming converter with the voltage, reactive power droop, or other zero-order reactive control schemes faces only the transient angle stability problem yet with a limited capacity for reactive power/power factor regulation. In contrast, the reactive power PI control scheme, as a first-order reactive control scheme, allows for constant reactive power/power factor operation. However, this control scheme or other first-order reactive control schemes may destabilize grid-forming converters through three transient stability problems-transient angle, voltage, and mixed stability problems. Moreover, we disclose the mechanisms behind these transient stability problems. Furthermore, we present a thorough comparison of typical reactive power control schemes. Finally, experimental results verify theoretical analyses.
ISSN:2168-6777
2168-6785
DOI:10.1109/JESTPE.2024.3477492