Asymmetric Sampling Disturbance-Based Universal Impedance Measurement Method for Converters
This letter proposes a universal impedance measurement method for grid-connected converter (GCC) where asymmetric disturbances are injected in the sampling process. The goal is to provide a low-cost and easy-implemented impedance measurement technique that does not rely on actual disturbance sources...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power electronics 2024-12, Vol.39 (12), p.15457-15461 |
---|---|
Hauptverfasser: | , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This letter proposes a universal impedance measurement method for grid-connected converter (GCC) where asymmetric disturbances are injected in the sampling process. The goal is to provide a low-cost and easy-implemented impedance measurement technique that does not rely on actual disturbance sources or prior controller knowledge. In this method, only two-phase sampling channels are needed to measure positive- and negative-sequence impedances of GCC at the same time. This method works well with converters employing various control strategies, and its universality is proved by theoretical analysis. The effectiveness of the proposed method is verified by the results of hardware-in-the-loop experiment and the testing of real prototype. |
---|---|
ISSN: | 0885-8993 1941-0107 |
DOI: | 10.1109/TPEL.2024.3451403 |