Peculiarities of nonsustained disruptive discharges at interruption of cable/line charging current
It has been found out that NSDD probability increases at cable/line charging current interruption compared with no-load test. This fact has been explained by formation of contact welds at closing of the preliminary charged cable/line. These welds being torn apart at the following contact partition m...
Gespeichert in:
Hauptverfasser: | , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | It has been found out that NSDD probability increases at cable/line charging current interruption compared with no-load test. This fact has been explained by formation of contact welds at closing of the preliminary charged cable/line. These welds being torn apart at the following contact partition may serve as a source of macroparticles or surface irregularities resulting in increased probability of NSDD. |
---|---|
DOI: | 10.1109/ISDEIV.2002.1027381 |