Short-line fault interruption capability of vacuum circuit breakers
Current zero measurements are performed during short-line fault interruption tests of vacuum circuit breakers. Various reignition modes (occurring between 0 and 75 ms after current zero) were observed due to insufficient arcing time. The (single) restrike and the (single) failure occurred with highe...
Gespeichert in:
Hauptverfasser: | , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Current zero measurements are performed during short-line fault interruption tests of vacuum circuit breakers. Various reignition modes (occurring between 0 and 75 ms after current zero) were observed due to insufficient arcing time. The (single) restrike and the (single) failure occurred with higher current than rated. The relationship between post-arc current/charge, reignition mode and TRV are discussed in this paper. All interrupters succeeded to interrupt at first or second current zero under the 'rated' conditions of short-line fault current and TRV. |
---|---|