Jetfire lab: Jetfire at reduced scale

This article addresses the development of a bench-scale test (jetfire lab) mimicking the fire exposure of the large-scale jetfire facility. An experimental approach was addressed to develop direct correlation and to validate the similitude between bench-scale test and large-scale jetfire. Comparison...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Journal of fire sciences 2021-11, Vol.39 (6), p.455-476, Article 07349041211037192
Hauptverfasser: Sarazin, Johan, Franchini, Elsa, Dréan, Virginie, Chiva, Roman, Bourbigot, Serge
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This article addresses the development of a bench-scale test (jetfire lab) mimicking the fire exposure of the large-scale jetfire facility. An experimental approach was addressed to develop direct correlation and to validate the similitude between bench-scale test and large-scale jetfire. Comparisons were made by testing Zaltex passive fire protection material in the form of panels. Novel setups were designed to make the jetfire lab able to measure time/temperature curves similar to those obtained at a large scale. The assembly of the tested samples was also investigated. An experimental protocol was elaborated to consider the junction between parts of the sample at the reduced scale. Direct correlation was found between the large and the bench scale and it was evidenced that jetfire lab can be used for preliminary study and development of new thermal barriers for fire protection.
ISSN:0734-9041
1530-8049
DOI:10.1177/07349041211037192