Preliminary feasibility analysis of a hybrid pumped-hydro energy storage system using abandoned coal mine goafs
•Technical feasibility of abandoned coal mine goafs used as reservoirs is analyzed.•The pumped-hydro energy storage system using one goaf has an efficiency of 82.8%.•For a typical mining area, the effective storage capacity can reach 1.58 × 106 m3.•Operating the proposed system in daily regulation m...
Gespeichert in:
Veröffentlicht in: | Applied energy 2020-01, Vol.258, p.114007, Article 114007 |
---|---|
Hauptverfasser: | , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | •Technical feasibility of abandoned coal mine goafs used as reservoirs is analyzed.•The pumped-hydro energy storage system using one goaf has an efficiency of 82.8%.•For a typical mining area, the effective storage capacity can reach 1.58 × 106 m3.•Operating the proposed system in daily regulation mode is viable in China.
Following the Paris climate agreement, a consensus has been made on the urgent need for increasing the use of clean energy and large-scale energy storage. This paper proposes a hybrid pumped-hydro energy storage system using goafs of abandoned coal mines. The performance of the energy storage system and the suitability potential of coal mine goafs serving as underground reservoirs were analyzed. Based on the designed conditions and meteorological data of a typical area (Inner Mongolia, China), the proposed system could have an average system efficiency of approx. 82.8% and a regulating-energy density of 1.06 kW·h/m3. Potential analysis for goafs serving as reservoirs show that a typical coal mine with a 3 × 5 km2 dimensions and 6 m coal thickness could have a usable capacity of 1.58 × 106 m3. To ensure the smooth exchange of water in goaf reservoirs, the permeability should be above 10−7 m2, corresponding to the usable coefficient (≥0.8) of goaf reservoirs. The minimum horizontal distance between two reservoirs with a typical geology has been set to 245 m so that the leakage rate could be smaller than 1%. A diameter of 1 m for vertical ventilation shafts is acceptable with respect to the air pressure loss (211 Pa). Based on the reckoning of the existing coal mine goaf space in China, it has been found that developing hybrid pumped-hydro energy storage plants using abandoned coal mine goafs for daily regulation is feasible in the short term. |
---|---|
ISSN: | 0306-2619 1872-9118 |
DOI: | 10.1016/j.apenergy.2019.114007 |