An assessment of indoor air quality in the maintenance room at Beirut-Rafic Hariri International Airport

In Beirut-Rafic Hariri International Airport (RHIA)-Lebanon, direct openings exist between the apron and the arrivals hall providing a pathway for contaminated air to enter the buildings. Also, airport employees spend no less than 12 h inside the airport's buildings and experience respiratory s...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Atmospheric pollution research 2019-05, Vol.10 (3), p.701-711
Hauptverfasser: Mokalled, Tharwat, Adjizian Gérard, Jocelyne, Abboud, Maher, Liaud, Céline, Nasreddine, Rouba, Le Calvé, Stéphane
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In Beirut-Rafic Hariri International Airport (RHIA)-Lebanon, direct openings exist between the apron and the arrivals hall providing a pathway for contaminated air to enter the buildings. Also, airport employees spend no less than 12 h inside the airport's buildings and experience respiratory symptoms. Therefore, the influence of Beirut-RHIA's activities on the indoor air quality of the maintenance room in the control tower (impact on employees) was the focus of this study. This is the first study to assess the speciation of 46 Volatile organic compounds (VOCs) in indoor air of an airport workplace. Measurements, conducted during June and October 2014, has focused, in particular, on nitrogen dioxide (NO2) and Volatile organic compounds (VOCs), key ozone and PM precursors emitted from aircraft exhaust. Gas chromatographic techniques (GC-FID) were used to assess the concentrations of 46 VOCs, whereas colorimetric methods were adopted to determine NO2 concentrations. In general, the concentrations of measured VOCs did not present any risks except for acrolein, and NO2 concentrations inside the maintenance room were significantly below the World Health Organization (WHO) annual threshold limit (40 μg m−3). An interesting correlation was observed between aircraft number and the concentration of light aldehydes/ketones measured in the maintenance room. This is the first study dedicated to assess the speciation of a large number of VOCs in a work place environment in Lebanon. •46 VOCs were measured inside the maintenance room at Beirut Airport.•Aircraft number and light aldehydes/ketones were correlated.•Indoor VOC concentrations were influenced by outdoor air.•Indoor NO2 levels were below WHO recommendations.
ISSN:1309-1042
1309-1042
DOI:10.1016/j.apr.2018.11.008